No
|
Fault Event Display
|
Parameters
|
Required Actions
|
|
1
|
Communication fault [B/D Type],[Board positon], [Fault Description]
|
[Fault Description]: SPI , I2C , IO CAN , Main CAN, UI CAN, Ext CAN, UART failure
|
Replace the Module on [B/D Type]. e.g. "Communication fault mA Input 4-1 IO CAN"
|
|
2
|
Memory fault [B/D Type], [Fault Description]
|
[Fault Description]: Internal RAM, External RAM , Code memory, EEPROM, Flash
|
Replace the Module on [B/D Type] e.g. "Memory fault mA Input EEPROM"
|
|
3
|
Catalog memory fault
|
NA
|
1. Update Calalog file by SD Card 2. Replace UI PCB
|
|
4
|
Internal hardware fault [B/D Type]
|
NA
|
Replace the Module on [B/D Type] e.g. "Internal hardware fault mA Input"
|
|
5
|
Sensor circuit fault CH: xx, Code: xxx
|
xx: Displayed channel number xxx: Code 0: Gain setting error, 1: signal conditioning circuit error
|
1. Check detector has failure output(0~1mA)- Resolve detector failure 2. Replace IO Module if detector was normal
|
|
6
|
Supplied voltage fault [B/D Type], Code: xxx
|
Code: xxx 0: Vapp low, 1: V5 low, 2: V3.3 low, 3: V12 low, 4: V9 low
|
Replace the Module by B/D Type. Note (1)
|
|
7
|
Internal software fault [B/D Type], Code: xxx
|
xxx: Code 0: BUFFER OVERFLOW, 1: instruction test failed, 2: Sequence Checking failed
|
Replace the Module by B/D Type. Note (1)
|
|
8
|
Modbus Comm Fault CH: xx, Node: xx
|
Reserved for MODBUS input
|
NA
|
|
9
|
Sensor Fault CH: xx, [B/D Type], Code: xx
|
xx: Displayed channel number yy: Code 0 : bead open/short 1 : line open/short 2 : detector short 3 : operating voltage fault 4 :driver current fault
|
1.Remove/replace failure of detector
2.Check wirings are correct
|
|
10
|
mA Output Error CH: xx
|
xx: Displayed channel number
|
Replace mA output module
|
|
11
|
Relay Output Error CH: xx
|
xx: Displayed channel number
|
Replace Relay module that
|
|
12
|
Detector In Fault CH: xx, [B/D Type]
|
xx: Displayed channel number
|
Remove fault of detector are connected.
|
|
13
|
Battery Fault [Enclosure]
|
Enclosure 0: master enclosure, 1: extension enclosure
|
Replace the battery
|
|
14
|
IO B/D Not Matched Slot: xx-x [Board position], Prev: xxx [B/D Type], Curr:xxx [B/DType]
|
[Board position]
[B/D Type]
|
1. Check if Module loose connection 2. Check if IO Module type are matched to information in LCD. 3. Replace IO Module to corrected one or try Module and channel configurations.
|
|
15
|
Negative Reading CH: xx, Conc: xxxx [Reading unit]
|
xx: Displayed channel number
|
1. Need gas calibration detectors or cell for the channel 2. Replace detector or cell 3. Need gas calibration TPPL channel
|
| 16 | Fault Cleared CH: xx, Code: xx | xx: Displayed channel number Code Code Number (1~17) | |
| 17 | Reset all faults | NA | |